A567, A571, Advanced program group (continued) – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 128
128
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Chapter 3
Programming and Parameters
Advanced Program Group (continued)
A567 [Max Traverse]
Sets the amplitude of triangle wave speed modulation.
Values
Default:
0.00 Hz
Min/Max:
0.00/300.00 Hz
Display:
0.01 Hz
Her
tz
Seconds
[Max Traverse]
[P Jump]
[Output Freq]
[Fiber Status]
Traverse Enable Bit
Traverse Bit
A568 [Traverse Inc]
Sets the time required for the Traverse function to accelerate from the minimum to the maximum traverse frequency. See the diagram at
[Max Traverse].
Values
Default:
0.00 s
Min/Max:
0.00/300.00 s
Display:
0.01 s
A569 [Traverse Dec]
Sets the time required for the Traverse function to decelerate from the maximum to the minimum traverse frequency. See the diagram at
[Max Traverse].
Values
Default:
0.00 s
Min/Max:
0.00/300.00 s
Display:
0.01 s
A570 [P Jump]
Sets the frequency amplitude that is added to or subtracted from the commanded frequency. See the diagram at
[Max Traverse].
Values
Default:
0.00 Hz
Min/Max:
0.00/300.00 Hz
Display:
0.01 Hz
A571 [Sync Time]
Related Parameter(s):
,
Enables the function that holds the drive at the current frequency even if the commanded frequency changes. Used with
[DigIn TermBlk xx] 32 “Sync Enable”.
Values
Default:
0.0 s
Min/Max:
0.0/3200.0 s
Display:
0.1 s
Hertz
Time
Speed Sync Bit
Change Ref's
[Sync Time]
Drive #1 and #2 Sync Enable Input
[Fiber Status]
New Drive #1 Reference
New Drive #2 Reference