T064 – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 84
84
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Chapter 3
Programming and Parameters
Options
48 “2-Wire FWD”
(only for DigIn TermBlk 02)
[DigIn TermBlk 02] default. Select 2-Wire FWD for this input.
Select this option and set
or
[Start Source x] to 2 “DigIn TrmBlk” to configure [Start Source x] to a 2-wire run
forward mode. Also see
[2-Wire Mode] for level trigger settings.
49 “3-Wire Start”
(only for DigIn TermBlk 02)
Select 3-Wire Start for this input.
Select this option and set
or
[Start Source x] to 2 “DigIn TrmBlk” to configure [Start Source x] to a 3-wire start
mode.
50 “2-Wire REV”
(only for DigIn TermBlk 03)
[DigIn TermBlk 03] default. Select 2-Wire REV for this input.
Select this option and set
or
[Start Source x] to 2 “DigIn TrmBlk” to configure [Start Source x] to a 2-wire run
reverse mode. Also see
[2-Wire Mode] for level trigger settings.
For PowerFlex 523 drives, this setting will be disabled If [DigIn TermBlk 03] is set to 7 “Preset Freq”.
51 “3-Wire Dir”
(only for DigIn TermBlk 03)
Select 3-Wire Dir for this input.
Select this option and set
or
[Start Source x] to 2 “DigIn TrmBlk” to change the direction of [Start Source x].
For PowerFlex 523 drives, this setting will be disabled If [DigIn TermBlk 03] is set to 7 “Preset Freq”.
52 “Pulse Train”
(PF523: only for DigIn TermBlk 05)
(PF525: only for DigIn TermBlk 07)
Select pulse train for this input.
Use
and
[Speed Referencex] to select pulse input.
Jumper for DigIn TermBlk 05 or 07 Sel must be moved to Pulse In.
(1) This function may be tied to one input only.
(2) Setting is specific to PowerFlex 525 drives only.
t064 [2-Wire Mode]
Related Parameter(s):
Stop drive before changing this parameter.
Programs the mode of trigger only for
[DigIn TermBlk 02] and
[DigIn TermBlk 03] when 2-wire option is being selected as
[Start Source x].
Options
0 “Edge Trigger” (Default)
Standard 2-Wire operation.
1 “Level Sense”
• I/O Terminal 01 “Stop” = Coast to stop. Drive will restart after a Stop command when:
– Stop is removed
and
– Start is held active
• I/O Terminal 03 “Run REV”
2 “Hi-Spd Edge”
• Outputs are kept in a ready-to-run state. The drive will respond to a Start command within 10 ms.
• I/O Terminal 01 “Stop” = Coast to stop.
• I/O Terminal 03 “Run REV”
3 “Momentary”
• Drive will start after a momentary input from either the Run FWD input (I/O Terminal 02) or the Run REV input (I/O Terminal
03).
• I/O Terminal 01 “Stop” = Stop according to the value set in
[Stop Mode].
ATTENTION: Hazard of injury exists due to unintended operation. When t064 [2-Wire Mode] is set to
option 1, and the Run input is maintained, the Run inputs do not need to be toggled after a Stop input for
the drive to run again. A Stop function is provided only when the Stop input is active (open).
IMPORTANT
There is greater potential voltage on the output terminals when using this option.