A434, A435, A433 – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 109: Ring, Advanced program group (continued)
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
109
Programming and Parameters
Chapter 3
Advanced Program Group (continued)
A433 [Purge Frequency]
Provides a fixed frequency command value when
,
[DigIn TermBlk xx] is set to 40 “Purge”.
Values
Default:
5.00 Hz
Min/Max:
0.00/500.00 Hz
Display:
0.01 Hz
A434 [DC Brake Time]
,
Sets the length of time that DC brake current is “injected” into the motor.
Values
Default:
0.0 s
Min/Max:
0.0/99.9 s
Display:
0.1 s
A435 [DC Brake Level]
Defines the maximum DC brake current, in amps, applied to the motor when
[Stop Mode] is set to either 4 “Ramp” or 6 “DC Brake”.
Values
Default:
Drive Rated Amps x 0.05
Min/Max:
0.00/(Drive Rated Amps x 1.80)
Display:
0.01 A
DC Injection Stop Mode
Volts/Speed
Voltage
Time
Stop Command
Speed
[DC Brake Time]
Volts/Speed
Ramp-to-Stop Mode
Time
Stop Command
Magnitude
depends on
[DC Brake Level]
Magnitude
depends on
[DC Brake Level]
[DC Brake Time]
Voltage
Speed
ATTENTION: If a hazard of injury due to movement of equipment or material exists, an auxiliary mechanical braking device must be used. This feature should
not be used with synchronous motors. Motors may be demagnetized during braking.
A436 [DC Brk Time@Strt]
,
Sets the length of time that DC brake current is “injected” into the motor after a valid start command is received.
Values
Default:
0.0 s
Min/Max:
0.0/99.9 s
Display:
0.1 s
Volts/Speed
Time
Start Command
[DC Brake Level]
[DC Brk Time@Strt]
Voltage
Speed