Environmental specifications – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 156
156
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Appendix A
Supplemental Drive Information
Environmental Specifications
EPRI
Electric Power Research Institute
Certified compliant with the following standards:
SEMI F47
IEC 61000-4-34
Lloyds Register
Not applicable
Lloyd’s Register Type Approval Certificate
12/10068(E1)
RoHS
Compliant with the European “Restriction of Hazardous Substances” Directive
The drive is also designed to meet the appropriate portions of the following specifications:
NFPA 70 - US National Electrical Code
NEMA ICS 7.1 - Safety standards for Construction and Guide for Selection, Installation and Operation of Adjustable
Speed Drive Systems.
Certifications
PowerFlex 523
PowerFlex 525
Specifications
PowerFlex 523
PowerFlex 525
Altitude:
Without derating:
With derating:
Current Derating Curves on page 17
for derating guidelines.
1000 m (3300 ft) max.
Up to 4000 m (13,200 ft) max., with the exception of 600V drives at 2000 m (6600 ft)
max.
Max. Surrounding Air
Temperature
Without derating:
With derating:
See
Current Derating Curves on page 17
for derating guidelines.
-20...50
°C (-4...122 °F)
-20...60
°C (-4...140 °F) or -20...70 °C (-4...158 °F) with optional Control Module Fan
kit.
Storage Temperature:
Frame A...D:
Frame E:
-40...85
°C (-40...185 °F)
-40...70 °C (-40...158 °F)
Atmosphere:
Relative Humidity:
0...95% noncondensing
Shock:
Vibration:
Complies with IEC 60068-2-27
Complies with IEC 60068-2-6:1995
Conformal Coating:
Complies with:
IEC 60721-3-3 to level 3C2 (chemical and gases only)
Surrounding Environment
Pollution Degree
Pollution Degree 1 & 2:
Pollution Degree Ratings According to EN 61800-5-1 on page 49
for descriptions.
All enclosures acceptable.
Sound Pressure Level
(A-weighted)
Frame A & B:
Frame C:
Frame D:
Frame E:
Measurements are taken 1 m from the drive.
Maximum 53 dBA
Maximum 57 dBA
Maximum 64 dBA
Maximum 68 dBA
IMPORTANT
Drive must not be installed in an area where the ambient atmosphere contains volatile or
corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must
be stored in an area where it will not be exposed to a corrosive atmosphere.
Frame
Size
Operating and Nonoperating
Nonoperating (Transportation)
Force
(Shock/Vibration)
Mounting Type
Force
(Shock/Vibration)
Mounting Type
A
15 g / 2 g
DIN rail or screw
30 g/ 2.5 g
Screw only
B
15 g / 2 g
DIN rail or screw
30 g/ 2.5 g
Screw only
C
15 g / 2 g
DIN rail or screw
30 g/ 2.5 g
Screw only
D
15 g / 2 g
Screw only
30 g/ 2.5 g
Screw only
E
15 g / 1.5 g
Screw only
30 g/ 2.5 g
Screw only