T088, T087, Terminal block group (continued) – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 89

Rockwell Automation Publication 520-UM001G-EN-E - September 2014
89
Programming and Parameters
Chapter 3
Terminal Block Group (continued)
t087 [EM Brk On Delay]
Sets the time the drive remains at minimum frequency (after releasing the brake coil relay) before stopping if EM Brake Control Mode is enabled with
[Stop Mode].
Values
Default:
2.00 s
Min/Max:
0.00/10.00 s
Display:
0.01 s
Frequency
Time
[Minimum Freq]
[EM Brk Off Delay]
[EM Brk On Delay]
Stop
commanded
Start
commanded
EM Brk
de-energized (On)
Drive stops
EM Brk
energized (Off)
Ramp accel
Ramp decel
t088 [Analog Out Sel]
PowerFlex 525 only.
The 0-10V, 0-20 mA or 4-2 0 mA analog output can be used to provide a signal proportional to several drive conditions. This parameter also selects which analog calibration parameters
to use.
Values
Default:
0
Min/Max:
0/23
Display:
1
PF 525
Options
Output Range
Minimum Output Value
Maximum Output Value =
[Analog Out High]
Filter
(1)
(1) Filter A is a single pole digital filter with a 162 ms time constant. Given a 0...100% step input from a steady state, the output of Filter A takes 500 ms to get to 95% of maximum, 810 ms to get to 99%,
and 910 ms to get to 100%.
Related
Parameter
0 “OutFreq 0-10”
0-10V
0V = 0 Hz
[Maximum Freq]
None
1 “OutCurr 0-10”
0-10V
0V = 0 A
200% Drive Rated Current
Filter A
2 “OutVolt 0-10”
0-10V
0V = 0 V
120% Drive Rated Output Volts
None
3 “OutPowr 0-10”
0-10V
0V = 0 kW
200% Drive Rated Power
Filter A
4 “OutTorq 0-10”
0-10V
0V = 0 A
200% Drive Rated Current
Filter A
5 “TstData 0-10”
0-10V
0V = 0000
65535 (Hex FFFF)
None
–
6 “Setpnt 0-10”
0-10V
0V = 0%
100.0% Setpoint setting
None
7 “DCVolt 0-10”
0-10V
0V = 0V
100.0% of trip value
None
8 “OutFreq 0-20”
0-20 mA
0 mA = 0 Hz
[Maximum Freq]
None
9 “OutCurr 0-20”
0-20 mA
0 mA = 0 A
200% Drive Rated Current
Filter A
10 “OutVolt 0-20”
0-20 mA
0 mA = 0 V
120% Drive Rated Output Volts
None
11 “OutPowr 0-20”
0-20 mA
0 mA = 0 kW
200% Drive Rated Power
Filter A
12 “OutTorq 0-20”
0-20 mA
0 mA = 0 A
200% Drive Rated Current
Filter A
13 “TstData 0-20”
0-20 mA
0 mA = 0000
65535 (Hex FFFF)
None
–
14 “Setpnt 0-20”
0-20 mA
0 mA = 0%
100.0% Setpoint setting
None
15 “DCVolt 0-20”
0-20 mA
0 mA = 0V
100.0% of trip value
None
16 “OutFreq 4-20”
4-20 mA
4 mA = 0 Hz
[Maximum Freq]
None
17 “OutCurr 4-20”
4-20 mA
4 mA = 0 A
200% Drive Rated Current
Filter A
18 “OutVolt 4-20”
4-20 mA
4 mA = 0 V
120% Drive Rated Output Volts
None
19 “OutPowr 4-20”
4-20 mA
4 mA = 0 kW
200% Drive Rated Power
Filter A
20 “OutTorq 4-20”
4-20 mA
4 mA = 0 A
200% Drive Rated Current
Filter A
21 “TstData 4-20”
4-20 mA
4 mA = 0000
65535 (Hex FFFF)
None
–
22 “Setpnt 4-20”
4-20 mA
4 mA = 0%
100.0% Setpoint setting
None
23 “DCVolt 4-20”
4-20 mA
4 mA = 0V
100.0% of trip value
None