Rockwell Automation Publication 520-UM001G-EN-E - September 2014

87

Programming and Parameters

Chapter 3

Terminal Block Group (continued)

(1) Setting is specific to PowerFlex 525 drives only.

t076 [Relay Out1 Sel]

Related Parameter(s):

P046

,

P048

,

P050

,

t070

,

t073

,

t077

,

t082

,

t086

,

t087

,

t093

,

t094

,

t097

,

A541

,

A564

t081 [Relay Out2 Sel]

PowerFlex 525 only.

Determines the operation of the programmable output relay.

Values

Default:
Relay Out1 Sel:
Relay Out2 Sel:

0
2

Min/Max:

0/29

Display:

1

PF 525

Options

Output Relay Changes State When...

Hysteresis

0 “Ready/Fault”

Relay changes state when power is applied. Indicates that the drive is ready for operation. Relay returns drive to
shelf state when power is removed or a fault occurs.

None

1 “At Frequency”

Drive reaches commanded frequency.

0.5 Hz above; 1.0 Hz below

2 “MotorRunning”

Motor is receiving power from the drive.

None

3 “Reverse”

Drive is commanded to run in reverse direction.

None

4 “Motor Overld”

Motor overload condition exists.

100 ms time delay on or off

5 “Ramp Reg”

Ramp regulator is modifying the programmed accel/ decel times to avoid an overcurrent or overvoltage fault from
occurring.

100 ms time delay on or off

6 “Above Freq”

Drive exceeds the frequency (Hz) value set in

t077

or

t082

[Relay Outx Level].

100 ms time delay on or off

7 “Above Cur”

Drive exceeds the current (% Amps) value set in

t077

or

t082

[Relay Outx Level].

100 ms time delay on or off

8 “Above DCVolt”

Drive exceeds the DC bus voltage value set in

t077

or

t082

[Relay Outx Level].

100 ms time delay on or off

9 “Retries Exst”

Value set in

A541

[Auto Rstrt Tries] is exceeded.

None

10 “Above Anlg V”

Analog input voltage (0-10V input) exceeds the value set in

t077

or

t082

[Relay Outx Level].

100 ms time delay on or off

11 “Above PF Ang”

Power Factor angle exceeds the value set in

t077

or

t082

[Relay Outx Level].

100 ms time delay on or off

12 “Anlg In Loss”

Analog input loss has occurred. Program

t094

[Anlg In V Loss] or

t097

[Anlg In mA Loss] for desired action when

input loss occurs.

On, 2 mA / ±1V
Off, 3 mA / ±1.5V

13 “ParamControl”

Output will be directly controlled by the state of the

t077

or

t082

[Relay Outx Level]. A value of 0 causes the output

to turn off. A value of 1 or greater in this parameter causes the output to turn on.

None

14 “NonRec Fault”

Value set in

A541

[Auto Rstrt Tries] is exceeded or

A541

[Auto Rstrt Tries] is not enabled or

A non-resettable fault has occurred.

None

15 “EM Brk Cntrl”

EM Brake is energized. Program

t087

[EM Brk On Delay] and

t086

[EM Brk Off Delay] for desired action.

None

16 “Thermal OL”

Relay energizes when thermal Motor overload counter is above the value set in

t077

or

t082

[Relay Outx Level]. It

also energizes if the drive is within 5

°C of the drive overheat trip point.

None

17 “Amb OverTemp”

Relay energizes when control module over temperature occurs.

None

18 “Local Active

Active when drive

P046

,

P048

or

P050

[Start Source x] is in local keypad control.

None

19 “Comm Loss”

Active when communication is lost from any comm source with reference or control.

None

20 “Logic In 1”

(1)

An input is programmed as “Logic Input 1” and is active.

None

21 “Logic In 2”

(1)

An input is programmed as “Logic Input 2” and is active.

None

22 “Logic 1 & 2”

(1)

Both Logic inputs are programmed and active.

None

23 “Logic 1 or 2”

(1)

One or both Logic inputs are programmed and one or both is active.

None

24 “StpLogic Out”

(1)

Drive enters StepLogic step with Command Word set to enable Logic output.

None

25 “Timer Out”

Timer has reached the value set in

t077

or

t082

[Relay Outx Level] or not timing.

None

26 “Counter Out”

Counter has reached the value set in

t077

or

t082

[Relay Outx Level] or not counting.

None

27 “At Position”

(1)

Drive is in Positioning mode and has reached the commanded position. Tolerance is adjusted with

A564

[Encoder

Pos Tol].

28 “At Home”

(1)

Drive is in Positioning mode and has reached the home position. Tolerance is adjusted with

A564

[Encoder Pos Tol]. –

29 “Safe-Off”

(1)

Both safe-off inputs are active.

IMPORTANT

Value for t077 or t082 [Relay Outx Level] must be entered in percent of drive rated output
current.

IMPORTANT

Do not use if

t093

[10V Bipolar Enbl] is set to 1 “Bi-Polar In”.