Chapter 3
Programming and Parameters
Basic Display Group (continued)
b007 [Fault 1 Code]
Related Parameter(s):
F604
-
F610
b008 [Fault 2 Code]
b009 [Fault 3 Code]
A code that represents a drive fault. Codes appear in these parameters in the order they occur (
[Fault 1 Code] = the most recent fault). Repetitive faults are only recorded once.
See
for more information.
Values
Default:
Read Only
Min/Max:
F0/F127
Display:
F0
b010 [Process Display]
,
32 bit parameter.
Output frequency scaled by [Process Disp Hi] and [Process Disp Lo].
Values
Default:
Read Only
Min/Max:
0/9999
Display:
1
32
b012 [Control Source]
,
,
,
-
A425
Active source of the Start Command and Frequency Command. Normally defined by the settings of
[Start Source x] and
[Speed Referencex].
See
Start and Speed Reference Control on page 46
for more information.
Values
Default:
Read Only
Min/Max:
0000/2165
Display:
0000
Start Command Source
Digit 1
1 = Keypad
2 = DigIn TrmBlk (Parameters
3 = Serial/DSI
4 = Network Opt
(1)
5 = EtherNet/IP
(2)
(1)
Select this setting if using the optional PowerFlex 25-COMM-E2P, 25-COMM-D, or
25-COMM-P adapters as the Start source and/or Frequency source.
(2)
Setting is specific to PowerFlex 525 drives only.
Frequency Command Source
Digit 2 & 3
00 = Other
01 = Drive Pot
02 = Keypad
03 = Serial/DSI
04 = Network Opt
(1)
05 = 0-10V Input
06 = 4-20mA Input
07 = Preset Freq (Parameters
-
A425
)
08 = Anlg In Mult
(2)
09 = MOP
10 = Pulse Input
11 = PID1 Output
12 = PID2 Output
(2)
(1)
14 = Encoder
(2)
15 = EtherNet/IP
(2)
16 = Positioning
(2)
Frequency Command Source
Digit 4
0 = Other (Digit 2 & 3 are used. Digit 4 is not shown.)
1 = Jog
2 = Purge
Not Used
Display reads...
Description
2004
Start source comes from Network Opt and Frequency source is Purge.
113
Start source comes from Serial/DSI and Frequency source comes from PID1 Output.
155
Start source and Frequency source comes from EtherNet/IP.
052
Start source comes from DigIn TrmBlk and Frequency source from 0-10V Input.
011
Start source comes from Keypad and Frequency source comes from Drive Pot.
Example