t062 [DigIn TermBlk 02]
t065 [DigIn TermBlk 05]
t063 [DigIn TermBlk 03]
t066 [DigIn TermBlk 06]
,
-
A425
,
A535
,
t067 [DigIn TermBlk 07]
PowerFlex 525 only.
t068 [DigIn TermBlk 08]
Stop drive before changing this parameter.
Programmable digital input. Changes to these inputs takes effect as soon as they are entered. If a digital input is set for a selection that is only usable on one input, no other input can
be set for the same selection.
Options
0 “Not Used”
Terminal has no function but can be read over network communications with
[Dig In Status].
1 “Speed Ref 2”
Selects
[Speed Reference2] as drive's speed command.
2 “Speed Ref 3”
Selects
[Speed Reference3] as drive's speed command.
3 “Start Src 2”
Selects
[Start Source 2] as control source to start the drive.
4 “Start Src 3”
Selects
[Start Source 3] as control source to start the drive.
5 “Spd + Strt 2”
[DigIn TermBlk 07] default.
Selects combination of
[Start Source 2] as speed command with control source to start the
drive.
6 “Spd + Strt 3”
Selects combination of
[Start Source 3] as speed command with control source to start the
drive.
7 “Preset Freq”
(PF523: only for DigIn TermBlk 03, 05,
and 06)
(PF525: only for DigIn TermBlk
05...08)
[DigIn TermBlk 05] and [DigIn TermBlk 06] default.
• Selects a preset frequency in Velocity mode (
[Speed Referencex] = 1...15). See
...
A425
[Preset Freq x].
• Selects a preset frequency and position in Positioning mode (
[Speed Referencex] = 16). See
[Step Units x] (only for PowerFlex 525 drives).
8 “Jog”
• When input is present, drive accelerates according to the value set in
[Jog Accel/Decel] and ramps to the value set in
[Jog Frequency].
• When input is removed, drive ramps to a stop according to the value set in
[Jog Accel/Decel].
• A valid Start command will override this input.
9 “Jog Forward”
[DigIn TermBlk 08] default.
Drive accelerates to
[Jog Accel/Decel] and ramps to a stop when input becomes inactive. A
valid Start command will override this input.
10 “Jog Reverse”
Drive accelerates to
[Jog Accel/Decel] and ramps to a stop when input becomes inactive. A
valid Start command will override this input.
11 “Acc/Dec Sel2”
(1)
If active, determines which Accel/Decel time will be used for all ramp rates except jog. Can be used with option 29 “Acc/Dec Sel3”
for additional Accel/Decel times. See
[Accel Time 2] for more information.
12 “Aux Fault”
When enabled, an
“Auxiliary Input” fault will occur when the input is removed.
13 “Clear Fault”
When active, clears an active fault.
14 “RampStop,CF”
Causes drive to immediately ramp to a stop regardless of how
[Stop Mode] is set.
15 “CoastStop,CF”
Causes drive to immediately coast to a stop regardless of how
[Stop Mode] is set.
16 “DCInjStop,CF”
Causes drive to immediately begin a DC Injection stop regardless of how
[Stop Mode] is set.
17 “MOP Up”
Increases the value of
[MOP Freq] at the rate set in
[MOP Time].
18 “MOP Down”
Decreases the value of
[MOP Time].
19 “Timer Start”
(1)
Clears and starts the timer function. May be used to control the relay or opto outputs.
20 “Counter In”
(1)
Starts the counter function. May be used to control the relay or opto outputs.
21 “Reset Timer”
Clears the active timer.
22 “Reset Countr”
Clears the active counter.
23 “Rset Tim&Cnt”
Clear the active timer and counter.
24 “Logic In 1”
(1)(2)
Logic function input number 1. May be used to control the relay or opto outputs (
[Relay Outx Sel] and
[Opto
Outx Sel], options 11...14). May be used in conjunction with StepLogic parameters
[Stp Logic x].
25 “Logic In 2”
(1)(2)
Logic function input number 2. May be used to control the relay or opto outputs (
[Relay Outx Sel] and
[Opto
Outx Sel], options 11...14). May be used in conjunction with StepLogic parameters
[Stp Logic x].
PF 525
IMPORTANT
Digital Inputs have priority for frequency control when programmed as Preset Speed and are active. See
Start Source and Speed Reference Selection on page 46
for more information.