T093, T089, T091 – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 90: T092, T090, Terminal block group (continued)
90
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Chapter 3
Programming and Parameters
Terminal Block Group (continued)
t089 [Analog Out High]
PowerFlex 525 only.
Scales the maximum output value (V or mA) when the source setting is at maximum.
Values
Default:
100%
Min/Max:
0/800%
Display:
1%
PF 525
t090 [Anlg Out Setpt]
PowerFlex 525 only.
Sets the percentage of output desired when
[Analog Out Sel] is set to 6, 14 or 22 “Analog Setpoint”.
Values
Default:
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%
PF 525
t091 [Anlg In 0-10V Lo]
Stop drive before changing this parameter.
Sets the percentage (based on 10V) of input voltage applied to the 0-10V analog input used to represent
[Minimum Freq].
Analog inversion can be accomplished by setting this value larger than
[10V Bipolar Enbl] is set to 1 “Bi-Polar In”, this parameter is ignored.
Values
Default:
0.0%
Min/Max:
0.0/200.0%
Display:
0.1%
t092 [Anlg In 0-10V Hi]
Stop drive before changing this parameter.
Sets the percentage (based on 10V) of input voltage applied to the 0-10V analog input used to represent
[Maximum Freq].
Analog inversion can be accomplished by setting this value smaller than
[Anlg In 0-10V Lo].
[10V Bipolar Enbl] is set to 1 “Bi-Polar In”, the same value applies to positive and negative voltage.
Values
Default:
100.0%
Min/Max:
0.0/200.0%
Display:
0.1%
t093 [10V Bipolar Enbl]
Related Parameter(s):
PowerFlex 525 only.
Enables/disables bi-polar control. In bi-polar mode direction is commanded by the polarity of the voltage.
If bi-polar control is enabled,
[Minimum Freq] and
[Anlg In 0-10V Lo] are ignored.
Options
0 “Uni-Polar In” (Default)
0-10V only
1 “Bi-Polar In”
±10V
PF 525