Fault and diagnostic group (continued) – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 132
132
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Chapter 3
Programming and Parameters
Fault and Diagnostic Group (continued)
F661 [Status @ Fault 1]
F663 [Status @ Fault 3]
F665 [Status @ Fault 5]
F662 [Status @ Fault 2]
F664 [Status @ Fault 4]
F666 [Status @ Fault 6]
F668 [Status @ Fault 8]
F670 [Status @ Fault10]
PowerFlex 525 only.
F667 [Status @ Fault 7]
F669 [Status @ Fault 9]
[Drive Status] with the most recent 10 faults occurred.
[Status@ Fault 1] stores the most recent fault, [Status@ Fault 2] stores the second most recent fault and [Status@ Fault 3] stores the third most recent fault.
Values
Default:
Read Only
Min/Max:
0/0x1F
Display:
1
PF 525
1 = Condition True, 0 = Condition False
Running
Digit 1
Forward
Digit 2
Accelerating
Digit 3
Decelerating
Digit 4
SafetyActive
(1)
Digit 5
(1)
Setting is specific to PowerFlex 525 drives only.
F681 [Comm Sts - DSI]
Displays the status of the RS485 serial (DSI) port to the drive.
Values
Default:
Read Only
Min/Max:
0000/1911
Display:
0000
1 = Condition True, 0 = Condition False
Rx
Digit 1
Tx
Digit 2
Status
Digit 3
Error
Digit 4
Not Used
Digit 3 (Connection Status)
0
“Not Active”
1
“Modbus slave network (external Modbus master)”
2
“Modbus multi-drive w/ internal com option master”
3
“Modbus multi-drive w/ embedded com master”
(1)
(1)
Setting is specific to PowerFlex 525 drives only.
4
“DSI peripheral connected”
5...8 “Reserved”
9
“RS-485 network faulted”
F682 [Comm Sts - Opt]
Displays the status of the internal communication to the drive.
Values
Default:
Read Only
Min/Max:
0000/1911
Display:
0000
1 = Condition True, 0 = Condition False
Rx
Digit 1
Tx
Digit 2
Status
Digit 3
Error
Digit 4
Not Used
Digit 3 = “Internal Com option”
0
“Not Active (no connection)”
1
“Internal option connected/active”
2...8 “Reserved”
9
“Internal com option faulted”