B018, Basic display group (continued) – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 74

74
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Chapter 3
Programming and Parameters
Basic Display Group (continued)
b018 [Power Saved]
Instantaneous power savings of using this drive compared to an across the line starter.
Values
Default:
Read Only
Min/Max:
0.00/655.35 kW
Display:
0.01 kW
b019 [Elapsed Run time]
Accumulated time drive is outputting power. Time is displayed in 10 hour increments.
Values
Default:
Read Only
Min/Max:
0/65535 x 10 hr
Display:
1 = 10 hr
b020 [Average Power]
Average power used by the motor since the last reset of the meters.
Values
Default:
Read Only
Min/Max:
0.00/(Drive Rated Power x 2)
Display:
0.01 kW
b021 [Elapsed kWh]
Accumulated output energy of the drive. When the maximum value of this parameter is reached, it resets to zero and
Values
Default:
Read Only
Min/Max:
0.0/100.0 kWh
Display:
0.1 kWh
b022 [Elapsed MWh]
Accumulated output energy of the drive.
Values
Default:
Read Only
Min/Max:
0.0/6553.5 MWh
Display:
0.1 MWh
b023 [Energy Saved]
Total energy savings of using this drive compared to an across the line starter since the last reset of the meters.
Values
Default:
Read Only
Min/Max:
0.0/6553.5 kWh
Display:
0.1 kWh
b024 [Accum kWh Sav]
Total approximate accumulated energy savings of the drive compared to using an across the line starter.
Values
Default:
Read Only
Min/Max:
0.0/6553.5 kWh
Display:
0.1 = 10 kWh