P034 [Motor NP FLA]
Sets the motor nameplate FLA. Used to assist the Autotune routine and motor control.
Values
Default:
Based on Drive Rating
Min/Max:
0.1/(Drive Rated Amps x 2)
Display:
0.1 A
P035 [Motor NP Poles]
Sets the number of poles in the motor.
Values
Default:
4
Min/Max:
2/40
Display:
1
P036 [Motor NP RPM]
Stop drive before changing this parameter.
Sets the rated nameplate rpm of the motor. Used to calculate the rated slip of the motor. To reduce the slip frequency, set this parameter closer to the motor synchronous speed.
Values
Default:
1750 rpm
Min/Max:
0/24000 rpm
Display:
1 rpm
P037 [Motor NP Power]
PowerFlex 525 only.
Sets the motor nameplate power. Used in PM regulator.
Values
Default:
Drive Rated Power
Min/Max:
0.00/Drive Rated Power
Display:
0.01 kW
PF 525
P038 [Voltage Class]
Stop drive before changing this parameter.
Sets the voltage class of 600V drives. Only applicable to 600V drives.
Options
2 “480V”
3 “600V” (Default)
P039 [Torque Perf Mode]
Related Parameter(s):
,
Stop drive before changing this parameter.
Selects the motor control mode.
Options
0 “V/Hz”
1 “SVC” (Default)
2 “Economize”
3 “Vector”
(1)
(1) Setting is specific to PowerFlex 525 drives only.