Fault and diagnostic group (continued) – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 131
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
131
Programming and Parameters
Chapter 3
Fault and Diagnostic Group (continued)
F631 [Fault 1 Freq]
F633 [Fault 3 Freq]
F635 [Fault 5 Freq]
F632 [Fault 2 Freq]
F634 [Fault 4 Freq]
F636 [Fault 6 Freq]
F638 [Fault 8 Freq]
F640 [Fault10 Freq]
PowerFlex 525 only.
F637 [Fault 7 Freq]
F639 [Fault 9 Freq]
Displays and stores the value of
[Output Freq] with the most recent 10 faults occurred.
[Fault 1 Freq] stores the most recent fault, [Fault 2 Freq] stores the second most recent fault and [Fault 3 Freq] stores the third most recent fault.
Values
Default:
Read Only
Min/Max:
0.00/500.00 Hz
Display:
0.01 Hz
PF 525
F641 [Fault 1 Current]
F643 [Fault 3 Current]
F645 [Fault 5 Current]
F642 [Fault 2 Current]
F644 [Fault 4 Current]
F646 [Fault 6 Current]
F648 [Fault 8 Current]
F650 [Fault10 Current]
PowerFlex 525 only.
F647 [Fault 7 Current]
F649 [Fault 9 Current]
Displays and stores the value of
[Output Current] with the most recent 10 faults occurred.
[Fault 1 Current] stores the most recent fault, [Fault 2 Current] stores the second most recent fault and [Fault 3 Current] stores the third most recent fault.
Values
Default:
Read Only
Min/Max:
0.00/(Drive Rated Amps x 2)
Display:
0.01 A
PF 525
F651 [Fault 1 BusVolts]
F653 [Fault 3 BusVolts]
F655 [Fault 5 BusVolts]
F652 [Fault 2 BusVolts]
F654 [Fault 4 BusVolts]
F656 [Fault 6 BusVolts]
F658 [Fault 8 BusVolts]
F660 [Fault10 BusVolts]
PowerFlex 525 only.
F657 [Fault 7 BusVolts]
F659 [Fault 9 BusVolts]
Displays and stores the value of
[DC Bus Voltage] with the most recent 10 faults occurred.
[Fault 1 BusVolts] stores the most recent fault, [Fault2 BusVolts] stores the second most recent fault and [Fault 3 BusVolts] stores the third most recent fault.
Values
Default:
Read Only
Min/Max:
0/1200VDC
Display:
1VDC
PF 525