Basic program group, P031 – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 76
76
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Chapter 3
Programming and Parameters
Basic Program Group
P030 [Language]
Language Support
Selects the language displayed. A reset or power cycle is required after selection is made.
Keypad/
LCD Display
RSLogix 5000/
Logix Designer
Connected
Components
Workbench
Options
1 English (Default)
Y
Y
Y
2 Français
Y
Y
Y
3 Español
Y
Y
Y
4 Italiano
Y
Y
Y
5 Deutsch
Y
Y
Y
6 Japanese
–
Y
–
7 Português
Y
Y
–
8 Chinese
Chinese Simplified
–
Y
Y
9 Reserved
10 Reserved
11 Korean
–
Y
–
12 Polish
(1)
Y
–
–
13 Reserved
14 Turkish
(1)
Y
–
–
15 Czech
(1)
Y
–
–
(1) Due to a limitation of the LCD Display, some of the characters for Polish, Turkish, and Czech will be modified.
P031 [Motor NP Volts]
Related Parameter(s):
,
Stop drive before changing this parameter.
Sets the motor nameplate rated volts.
Values
Default:
Drive Rated Volts
Min/Max:
10V (for 230V Drives), 20V (for 460V Drives), 25V (for 600V Drives)/Drive Rated Volts
Display:
1V
P032 [Motor NP Hertz]
,
Stop drive before changing this parameter.
Sets the motor nameplate rated frequency.
Values
Default:
60 Hz
Min/Max:
15/500 Hz
Display:
1 Hz
P033 [Motor OL Current]
Related Parameter(s):
,
Sets the motor nameplate overload current. Used to determine motor overload conditions and can be set from 0.1 A to 200% of drive rated current.
Values
Default:
Drive Rated Amps
Min/Max:
0.0/(Drive Rated Amps x 2)
Display:
0.1 A
IMPORTANT
The drive will fault on an F007 “Motor Overload” if the value of this parameter is exceeded by 150% for 60 s.