beautypg.com

Accel/decel selection – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 48

background image

48

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Chapter 1

Installation/Wiring

Accel/Decel Selection

The Accel/Decel rate can be obtained by a variety of methods. The default rate is
determined by

P041

[Accel Time 1] and

P042

[Decel Time 1]. Alternative

Accel/Decel rates can be made through digital inputs, communications and/or
parameters. See below for the override priority.

(1) Setting is specific to PowerFlex 525 drives only.

Purge Input Enabled

AND Active

Terminal Block Jog

Input Enabled AND

Active

Input(s) is

programmed as

Acc/Dec

(2/3/4)

Is speed controlled

by [Preset Freq x]

Active

[Speed Referencex]

= Comms

Active

[Speed Referencex]

= 13 (Step Logic)

(1)

Drive stopped

(NOT running)

Accel/Decel always

Accel/Decel 1.

Accel/Decel from

[Jog Acc/Dec].

Accel/Decel 2 is active

when input is selected

by Accel and Decel input.

Drive uses Accel 1

and Decel 1.

No

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Accel/Decel 1/2/3/4 is

selected by the default

[Preset Freq x] setting.

Accel/Decel 1 or 2 is

selected according

to Comms.

Accel/Decel 1/2/3/4 is

selected according to

Step Logic

Active [DigIn TermBlk xx]

= 32 (Sync Enable)

[Sync Time] is used

for Accel/Decel rate

No

Yes

Traverse active if

[Max Traverse] > 0 Hz

Traverse Inc/Dec

is used for

Accel/Decel rate

No

Yes

This manual is related to the following products: