Installation/Wiring
Chapter 1
PowerFlex 523 Control I/O Terminal Block
PowerFlex 523 Control I/O Wiring Block Diagram
Control I/O Wiring Block Diagram Notes
(1) See
Digital Input Selection for Start Source on page 47
for more information on configuring the digital inputs.
IMPORTANT
I/O Terminal 01 is always a stop input. The stopping mode is determined by the
drive setting. See the tables below for more information.
Start Method
Stop Method
P046, P048, P050 [Start Source x]
I/O Terminal 01 Stop
Normal Stop
1 “Keypad”
Coast
Per P045
[Stop Mode]
2 “DigIn TrmBlk”
See
t062, t063 [DigIn TermBlk xx]
below
3 “Serial/DSI”
Coast
4 “Network Opt”
Coast
5 “Ethernet/IP”
(1)
(1) Setting is specific to PowerFlex 525 drives only.
Coast
04
05
06
01
02
03
11
12
13
14
15
C1
C2
Digital Common
DigIn TermBlk 05/Pulse
DigIn TermBlk 06
Stop
(1)
DigIn TermBlk 02/
Start/Run FWD
(2)
DigIn TermBlk 03/
Direction/Run REV
R1
R2
Relay N.O.
Relay Common
+24V DC
+10V DC
0-10V Input
Analog Common
4-20mA Input
RJ45 Shield
Comm Common
+24V
+10V
Typical
SNK wiring
Typical
SRC wiring
R1
11
12
13
14
15
C1
C2
R2
R3
01
02
03
04
05
06
Pot must be
1...10 k ohm
2 W min.
SNK
D
igital In
D
igIn
TermBlk 05 S
el
J7
J8
Pulse In
SRC
Digital
Input
SRC
SNK
R3
Relay N.C.
81
RS485
(DSI)