Programming and Parameters

Chapter 3

Advanced Program Group (continued)

A456 [PID 1 Trim Hi]

A468 [PID 2 Trim Hi]

PowerFlex 525 only.

Scales the upper value of the trim frequency when trim is active.

Values

Default:

60.0 Hz

Min/Max:

0.0/500.0 Hz

Display:

0.1 Hz

PF 525

A457 [PID 1 Trim Lo]

A469 [PID 2 Trim Lo]

PowerFlex 525 only.

Scales the lower value of the trim frequency when trim is active.

Values

Default:

0.0 Hz

Min/Max:

0.0/500.0 Hz

Display:

0.1 Hz

PF 525

A458 [PID 1 Trim Sel]

A470 [PID 2 Trim Sel]

PowerFlex 525 only.

Stop drive before changing this parameter.

Sets the PID output as trim to the source reference.

Options

0 “Disabled” (Default)

PID Trim is disabled.

1 “TrimOn Pot”

2 “TrimOn Keypd”

3 “TrimOn DSI”

4 “TrimOn NetOp”

5 “TrimOn 0-10V”

6 “TrimOn 4-20”

7 “TrimOn Prset”

8 “TrimOn AnMlt”

(1)

9 “TrimOn MOP”

10 “TrimOn Pulse”

11 “TrimOn Slgic”

(1)

12 “TrimOn Encdr”

(1)

13 “TrimOn ENet”

(1)

(1) Setting is specific to PowerFlex 525 drives only.