C133, C136, C137 – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 96: C140, Communications group (continued)
96
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Chapter 3
Programming and Parameters
Communications Group (continued)
C133 [EN Subnet Cfg 1]
Related Parameter(s):
C134 [EN Subnet Cfg 2]
C135 [EN Subnet Cfg 3]
C136 [EN Subnet Cfg 4]
PowerFlex 525 only.
Sets the bytes of the subnet mask. A reset or power cycle is required after selection is made.
Values
Default:
0
Min/Max:
0/255
Display:
1
PF 525
255.255.255.0
[EN Subnet Cfg 1]
[EN Subnet Cfg 2]
[EN Subnet Cfg 3]
[EN Subnet Cfg 4]
IMPORTANT
C128 [EN Addr Sel] must be set to 1 “Parameters”.
C137 [EN Gateway Cfg 1]
Related Parameter(s):
C138 [EN Gateway Cfg 2]
C139 [EN Gateway Cfg 3]
C140 [EN Gateway Cfg 4]
PowerFlex 525 only.
Sets the bytes of the gateway address. A reset or power cycle is required after selection is made.
Values
Default:
0
Min/Max:
0/255
Display:
1
PF 525
192.168.1.1
[EN Gateway Cfg 1]
[EN Gateway Cfg 2]
[EN Gateway Cfg 3]
[EN Gateway Cfg 4]
IMPORTANT
C128 [EN Addr Sel] must be set to 1 “Parameters”.
C141 [EN Rate Cfg]
PowerFlex 525 only.
Sets the network data rate at which EtherNet/IP communicates. A reset or power cycle is required after selection is made.
Options
0 “Auto detect” (Default)
1 “10Mbps Full”
2 “10Mbps Half”
3 “100Mbps Full”
4 “100Mbps Half”
PF 525