Motor does not start – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 151

Rockwell Automation Publication 520-UM001G-EN-E - September 2014
151
Troubleshooting
Chapter 4
Motor does not Start.
Drive does not Start from Start or Run Inputs wired to the terminal
block.
Cause(s)
Indication
Corrective Action
No output voltage to the motor.
None
Check the power circuit.
• Check the supply voltage.
• Check all fuses and disconnects.
Check the motor.
• Verify that the motor is connected properly.
Check the control input signals.
• Verify that a Start signal is present. If 2-Wire control is used, verify that either the Run
Forward or Run Reverse signal is active, but not both.
• Verify that I/O Terminal 01 is active.
• Verify that
[Start Source x] matches your configuration.
• Verify that
[Reverse Disable] is not prohibiting movement.
• Verify that safety inputs (Safety 1 and Safety 2) are active.
Improper boost setting at initial start-up.
None
[Boost Select] to 2 “35.0, VT”.
Drive is Faulted
Flashing red status light
Clear fault.
• Press Stop if
[Stop Mode] is set to a value between “0” and “3”.
• Cycle drive power.
• Set
[Fault Clear] to 1 “Reset Fault” or 2 “Clear Buffer”.
• Cycle digital input if
[DigIn TermBlk xx] is set to
13 “Clear Fault”.
Incorrect programming.
•
,
[Start Source x] is set incorrectly.
None
Check setting for
[Control Source].
Incorrect input wiring.
See
for wiring examples.
• 2 wire control requires Run Forward, Run Reverse or Jog
input.
• 3 wire control requires Start and Stop inputs
• Stop input is always required.
None
• Wire inputs correctly and/or install jumper.
• If the PowerFlex 525 Safe-Torque-Off function is used, verify that inputs are active.
• If 2-wire or 3-wire mode is used, verify that
[DigIn TermBlk 02] and
[DigIn
TermBlk 03] are set properly.
Incorrect Sink/Source jumper setting.
None
Set switch to match wiring scheme.
Cause(s)
Indication
Corrective Action
Drive is Faulted
Flashing red status light
[Stop Mode] is set to a value between “0” and “3”.
[Fault Clear] to 1 “Reset Fault” or 2 “Clear Buffer”.
• Cycle digital input if
[DigIn TermBlk xx] is set to
13 “Clear Fault”.
Incorrect programming.
•
,
[Start Source x] is set incorrectly.
•
,
[DigIn TermBlk 02/03] is set incorrectly.
None
Check parameter settings.
Incorrect input wiring.
See
for wiring examples.
• 2 wire control requires Run Forward, Run Reverse or Jog
input.
• 3 wire control requires Start and Stop inputs
• Stop input is always required.
None
• Wire inputs correctly and/or install jumper.
• If the PowerFlex 525 Safe-Torque-Off function is used, verify that inputs are active.
Incorrect Sink/Source jumper setting.
None
Set switch to match wiring scheme.