Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 43

background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

43

Installation/Wiring

Chapter 1

2 Wire SRC Control -
Non-Reversing
P046 [Start Source 1] = 2
and t062 [DigIn TermBlk
02] = 48
Input must be active for
the drive to run. When
input is opened, the drive
will stop as specified by

P045

[Stop Mode].

If desired, a User Supplied
24V DC power source can
be used. Refer to the
“External Supply (SRC)”
example.

Internal Supply (SRC)

External Supply (SRC)

Each digital input draws 6 mA.

2 Wire SNK Control -
Non-Reversing

Internal Supply (SNK)

2 Wire SRC Control -
Run FWD/Run REV
P046 [Start Source 1] = 2,
t062 [DigIn TermBlk 02]
= 48 and t063 [DigIn
TermBlk 03] = 50
Input must be active for
the drive to run. When
input is opened, the drive
will stop as specified by

P045

[Stop Mode].

If both Run Forward and
Run Reverse inputs are
closed at the same time,
an undetermined state
could occur.

Internal Supply (SRC)

External Supply (SRC)

Each digital input draws 6 mA.

2 Wire SNK Control -
Run FWD/Run REV

Internal Supply (SNK)

3 Wire SRC Control -
Non-Reversing
P046 [Start Source 1] = 2,
t062 [DigIn TermBlk 02]
= 49 and t063 [DigIn
TermBlk 03] = 51
A momentary input will
start the drive. A stop
input to I/O Terminal 01
will stop the drive as
specified by

P045

[Stop

Mode].

Internal Supply (SRC)

External Supply (SRC)

Each digital input draws 6 mA.

I/O

Connection Example

11

01
02

Stop-Run

+24V Common

01
02

04

Stop-Run

Stop-Run

01
02
03
04

11

01
02
03

Stop-Run

Forward

Stop-Run

Reverse

Common

01
02
03
04

Stop-Run

Forward

Stop-Run

Reverse

+24V

Stop-Run

Forward

Stop-Run

Reverse

01
02
03
04

11

01
02

Stop

Start

01
02

04

+24V

Common

Stop

Start