Smart start-up with basic program group parameters, Smart – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 61

Rockwell Automation Publication 520-UM001G-EN-E - September 2014
61
Start Up
Chapter 2
Smart Start-Up with Basic
Program Group Parameters
The PowerFlex 520-series drive is designed so that start up is simple and efficient.
The Basic Program Group contains the most commonly used parameters. See
Programming and Parameters on page 65
for detailed descriptions of the
parameters listed here, as well as the full list of available parameters.
Polish
(1)
Y
–
–
Turkish
(1)
Y
–
–
Czech
(1)
Y
–
–
(1) Due to a limitation of the LCD Display, some of the characters for Polish, Turkish, and Czech will be modified.
Language
Keypad/LCD Display
RSLogix 5000/
Logix Designer
Connected Components
Workbench
= Stop drive before changing this parameter.
= Parameter is specific to PowerFlex 525 drives only.
No.
Parameter
Min/Max
Display/Options
Default
P030
[Language]
1/15
1 = English
2 = Français
3 = Español
4 = Italiano
5 = Deutsch
6 = Reserved
7 = Português
8 = Reserved
9 = Reserved
10 = Reserved
11 = Reserved
12 = Polish
13 = Reserved
14 = Turkish
15 = Czech
1
Selects the language displayed.
Important: The setting takes effect after the drive
is power cycled.
P031
[Motor NP Volts]
10V (for 200V Drives), 20V
(for 400V Drives), 25V (for
600V Drives)/Drive Rated
Volts
1V
Based on Drive Rating
Sets the motor nameplate rated volts.
P032
[Motor NP Hertz]
15/500 Hz
1 Hz
60 Hz
Sets the motor nameplate rated frequency.
P033
[Motor OL Current]
0.0/(Drive Rated Amps x 2)
0.1 A
Based on Drive Rating
Sets the motor nameplate overload current.
P034
[Motor NP FLA]
0.0/(Drive Rated Amps x 2)
0.1 A
Drive Rated Amps
Sets the motor nameplate FLA.
P035
[Motor NP Poles]
2/40
1
4
Sets the number of poles in the motor.
P036
[Motor NP RPM]
0/24000 rpm
1 rpm
1750 rpm
Sets the rated nameplate rpm of motor.
P037
[Motor NP Power]
0.00/Drive Rated Power
0.01 kW
Drive Rated Power
Sets the motor nameplate power. Used in PM
regulator.
P038
[Voltage Class]
2/3
2 = “480V”
3 = “600V”
3
Sets the voltage class of 600V drives. Only applicable
to 600V drives.
P039
[Torque Perf Mode]
0/3
0 = “V/Hz”
1 = “SVC”
2 = “Economize”
3 = “Vector”
(1)
1
Selects the motor control mode.
(1) Setting is specific to PowerFlex 525 drives only.
PF 525
PF 525