T070, T075, T073 – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 86: Terminal block group (continued)

86
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Chapter 3
Programming and Parameters
Terminal Block Group (continued)
t070 [Opto Out1 Level]
Related Parameter(s):
t073 [Opto Out2 Level]
32 bit parameter.
PowerFlex 525 only.
Determines the on/off point for the digital outputs when
[Opto Outx Sel] is set to the values shown below.
Values
Default:
0
Min/Max:
0/9999
Display:
1
32
PF 525
Min/Max Value Range Based On [Opto Outx Sel] Setting
6:
0...500 Hz
10: 0...100%
16: 0.1...9999 s
20: 0/1
7:
0...180%
11 0/1
17: 1...9999 counts 26: 0...150%
8:
0...815V
13 0...800
18: 0...180
°
–
t075 [Opto Out Logic]
PowerFlex 525 only.
Determines the logic (Normally Open/NO or Normally Closed/NC) of the digital outputs only.
Values
Default:
0
Min/Max:
0/3
Display:
1
PF 525
Setting Digital Out 1 Logic Digital Out 2 Logic
0
NO
NO
1
NC
NO
2
NO
NC
3
NC
NC