T095, T096, T094 – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 91: T097, Terminal block group (continued)
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
91
Programming and Parameters
Chapter 3
Terminal Block Group (continued)
t094 [Anlg In V Loss]
,
Sets the response to a loss of input. When the 0-10V input (or –10 to +10V) is used for any reference, any input less than 1V is reported as a signal loss. Input must exceed 1.5V for the
signal loss condition to end.
If enabled, this function affects any input that is being used as a speed reference, PID reference or PID setpoint in the drive.
Options
0 “Disabled” (Default)
1 “Fault (F29)”
2 “Stop”
3 “Zero Ref”
4 “Min Freq Ref”
5 “Max Freq Ref”
6 “Key Freq Ref”
7 “MOP Freq Ref”
8 “Continu Last”
t095 [Anlg In4-20mA Lo]
Related Parameter(s):
Stop drive before changing this parameter.
Sets the percentage (based on 4-20 mA) of input current applied to the 4-20 mA analog input used to represent
[Minimum Freq].
Analog inversion can be accomplished by setting this value larger than
Values
Default:
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%
t096 [Anlg In4-20mA Hi]
Related Parameter(s):
Stop drive before changing this parameter.
Sets the percentage (based on 4-20 mA) of input current applied to the 4-20 mA analog input used to represent
[Maximum Freq].
Analog inversion can be accomplished by setting this value smaller than
[Anlg In4-20mA Lo].
Values
Default:
100.0%
Min/Max:
0.0/200.0%
Display:
0.1%
t097 [Anlg In mA Loss]
,
Sets the response to a loss of input. When the 4-20mA input is used for any reference, any input less than 2 mA is reported as a signal loss. Input must exceed 3 mA for the signal loss
condition to end.
If enabled, this function affects any input that is being used as a speed reference or PID reference or PID setpoint in the drive.
Options
0 “Disabled” (Default)
1 “Fault (F29)”
2 “Stop”
3 “Zero Ref”
4 “Min Freq Ref”
5 “Max Freq Ref”
6 “Key Freq Ref”
7 “MOP Freq Ref”
8 “Continu Last”