Velocity steplogic parameters – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 201
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
201
Velocity StepLogic, Basic Logic and Timer/Counter Functions
Appendix D
Velocity StepLogic
Parameters
DigIn TermBlk 06
Reset Counter
Limit Switch
DigIn TermBlk 05
Counter In
Photo Eye
Start
Output
Frequency
Relay Out
Code Descriptions for Parameters L180...L187
Digit 4
Digit 3
Digit 2
Digit 1
0
0
F
1
Digit 4 – Defines the action during the step currently executing
Setting
Accel/Decel Parameter
Used
StepLogic Output State
Commanded Direction
0
1
Off
FWD
1
1
Off
REV
2
1
Off
No Output
3
1
On
FWD
4
1
On
REV
5
1
On
No Output
6
2
Off
FWD
7
2
Off
REV
8
2
Off
No Output
9
2
On
FWD
A
2
On
REV
b
2
On
No Output
Digit 3 – Defines what step to jump to or how to end program when the logic conditions specified
in Digit 2 are met.
Setting
Logic
0
Jump to Step 0
1
Jump to Step 1
2
Jump to Step 2
3
Jump to Step 3
4
Jump to Step 4
5
Jump to Step 5
6
Jump to Step 6
7
Jump to Step 7
8
End Program (Normal Stop)
9
End Program (Coast to Stop)
A
End Program and Fault (F002)