Maximum motor cable length must not exceed the maximum length
indicated in
PowerFlex 520-Series RF Emission Compliance and
Installation Requirements on page 52
for compliance with radio frequency
emission limits for the specific standard and installation environment.
Connections and Grounding
(1) Some installations require a shielded enclosure. Keep wire length as short as possible between the enclosure entry point and the
EMI filter.
Additional Installation Requirements
This section provides information on additional requirements for Class C1 and
C2 installation, such as enclosures and EMC cores.
PowerFlex 520-Series RF Emission Compliance and Installation Requirements
Filter Type
Standard/Limits
EN61800-3 Category C1
EN61000-6-3
CISPR11 Group 1 Class B
EN61800-3 Category C2
EN61000-6-4
CISPR11 Group 1 Class A
(Input power ≤ 20 kVA)
EN61800-3 Category C3
(I ≤ 100 A)
CISPR11 Group 1 Class A
(Input power > 20 kVA)
Internal
–
10 m (33 ft)
20 m (66 ft)
External
(1)
(1) See
for more information on optional external filters.
30 m (16 ft)
100 m (328 ft)
100 m (328 ft)
IMPORTANT
EMC cores are included with:
• drives that have an internal EMC filter (25x-xxxxN114)
• external EMC filter accessory kit (25-RFxxx)
IMPORTANT
An enclosure, shielded input cable, and EMC cores are not required to meet
class C3 requirements.
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
EMI fittings and metal conduit
IP 30/NEMA 1/UL Type 1
option kit or EMC kit
Shielded enclosure(1)
Building structure steel
Enclosure ground connection
EMI filter
L1'
L2'
L3'
L1
L2
L3
Shielded motor cable