PID Set Up
Appendix F
•
A459 [PID 1 Ref Sel] = 6 “4-20mA Input”
PID Deadband
and
[PID x Deadband] are used to set a range, in percent,
of the PID Reference that the drive will ignore.
Example
•
A465 [PID 1 Deadband] = 5.0%
•
The PID Reference is 25.0%
•
The PID Regulator will not act on a PID Error that falls between 20.0 and
30.0%
PID Preload
[PID x Preload], in Hz, will be pre-loaded into
the integral component of the PID at any start or enable. This will cause the
drive’s frequency command to initially jump to that preload frequency, and the
PID loop starts regulating from there.
PID Limits
and
[PID x Trim Hi] and
[PID x Trim Lo] are used
to limit the PID output and are only used in trim mode. [PID x Trim Hi] sets the
maximum frequency for the PID output in trim mode. [PID x Trim Lo] sets the
reverse frequency limit for the PID output in trim mode. Note that when the
0 10 20 30 40 50 60 70 80 90 100
PID Reference (%)
4-20 mA Input
4
8
12
16
20
24
PID Enabled
Freq Cmd
PID Output
PID Pre-load Value
PID Pre-load Value > 0