beautypg.com

Pid deadband, Pid preload, Pid limits – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 219

background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

219

PID Set Up

Appendix F

A459 [PID 1 Ref Sel] = 6 “4-20mA Input”

PID Deadband

Parameters

A465

and

A477

[PID x Deadband] are used to set a range, in percent,

of the PID Reference that the drive will ignore.

Example

A465 [PID 1 Deadband] = 5.0%

The PID Reference is 25.0%

The PID Regulator will not act on a PID Error that falls between 20.0 and
30.0%

PID Preload

The value set in

A466

or

A478

[PID x Preload], in Hz, will be pre-loaded into

the integral component of the PID at any start or enable. This will cause the
drive’s frequency command to initially jump to that preload frequency, and the
PID loop starts regulating from there.

PID Limits

A456

and

A468

[PID x Trim Hi] and

A457

and

A469

[PID x Trim Lo] are used

to limit the PID output and are only used in trim mode. [PID x Trim Hi] sets the
maximum frequency for the PID output in trim mode. [PID x Trim Lo] sets the
reverse frequency limit for the PID output in trim mode. Note that when the

0 10 20 30 40 50 60 70 80 90 100

PID Reference (%)

4-20 mA Input

4

8

12

16

20

24

PID Enabled

Freq Cmd

PID Output

PID Pre-load Value

PID Pre-load Value > 0

This manual is related to the following products: