EAGLE QUANTUM PREMIER CONFIG.
11-9
EAGLE QUANTUM PREMIER CONFIG.
Version 6.0
Once the event name is entered and the comparison
configured, the event tracking configuration is set up using
the check boxes and menus to the right of the event name.
The five checkbox selections are defined below:
P: Printer (Tractor feed event printer)
D: Disk (Daily log file)
W: Window (One line FIFO display)
AC: Auto Clear (Event directly tracks the “raw” data state and
doesn’t require operator acknowledgement)
FL: Fault (Designates the event to be considered a fault
instead of an alarm).
In the completed sample
above, when the analog
value exceeds 29 the event
“30 Seconds Remaining”
will be logged to the printer
(in red), daily log file, event
window and the OIS will play
the “Warning” sound.
When the value drops below
29 the event will automatically
clear.
Selecting a “Monitored Global” display its associated configuration data in the “Configuration” pane to the right
of the globals list.
This provides “at a glance” a complete configuration overview of the selected global.
COMMAND BAR • GLOBALS
COMMAND BAR • GLOBALS