Standard signal processing, Eagle quantum premier devices, Uv and ir sensor sensitivity settings – Det-Tronics S3 Graphics User Manual
Page 170: Combined settings, Alarm latching mode

EAGLE QUANTUM PREMIER DEVICES
12-55
EAGLE QUANTUM PREMIER DEVICES
Version 6.0
Standard Signal Processing
Standard signal processing is recommended for high speed suppression systems only. To allow for high speed
operation, the standard processing mode does not incorporate the arc rejection programming.
This mode should only be used in a controlled, indoor environment.
UV and IR Sensor Sensitivity Settings
Both the UV and IR detectors can be individually programmed to operate in one of four sensitivity settings; Low,
Medium, High or Very High.
The sensitivity level determines the maximum response distance and the response for the UVIR flame detector
as a whole will be the lesser of the two.
Examples of sensitivity settings are shown in the table below:
Combined Settings
The bottom portion of the dialog box contains settings for the alarm latching, Optical Integrity (Oi), input time
delay and PV deadband adjustments that apply to the whole detector as opposed to a specific sensor.
Alarm Latching Mode
The red LED on the face of the
detector comes on when in alarm
and can be configured to be either
latching or non-latching. If latching
is selected, following a fire detection,
the LED will stay on until the detector
is reset from the point display for
the detector in the S
3
software.
The default is non-latching.
Sensitivity
Arc Rejection
30 Inch Methane
1 Sq. Ft. Gasoline
1 Sq. Ft. Methanol
UV
Standard
Low
40
30
15
Medium
60
45
20
High
80
65
35
Very High
100
100
55
UV Arc
Rejection
Low
Medium
35
30
10
Low
High
35
30
10
Medium
Medium
55
40
15
Medium
High
55
40
15
High
Medium
60
50
25
High
High
65
50
25
Very High
Medium
85
65
50
Very High
High
85
65
50
IR
Low
40
65
40
Medium
55
75
45
High
65
90
55
Very High
90
100
60
EQ2200UVIR • PROCESSING MODE