Eqp logic editor – Det-Tronics S3 Graphics User Manual
Page 239

13-14
EQP LOGIC EDITOR
Version 6.0
EQP LOGIC EDITOR
AB Table Settings
This menu selection opens a dialog box which allows up to
eight communication interface “tables” to be configured
to allow for data to be “moved” between the Eagle
Quantum Premier controller and an Allen-Bradley PLC
or other system utilizing Allen Bradley communication
protocols. Clicking on any cell in the “File Type” column
will activate a pop-up menu allowing the selection of the
proper table type for the data to be exchanged.
The three file types are binary, floating point (Float) and
Integer. To configure a table, select the appropriate file
type, file number, starting address and the number of
words to read (count). Once the tables are configured,
click the “OK” button to allocate memory to support the
new table configuration.
In the example above, table 1 is configured for binary data which will be stored in file 20. The table will be 128
words (16 bit registers) long and therefore support 2048 discrete “bits” of information.
MODBUS Export/Import
This selection allows the MODBUS settings created to be exported or imported to and from MS Excel or a text
editing program.
MODBUS Monitor
This dialog box is a tool for checking the value of data in any of the three configurable data tables used for
exchanging data between the Premier controller and Modbus RTU systems.
The desired table is selected with a radio button in the
top portion of the dialog box and a scrolling list displays
the data.
In the example to the right, the viewer has just been
activated and is attempting to establish communication
with the Premier controller.
LOGIC EDITOR • CONTROLLER MENU