Eqp logic editor – Det-Tronics S3 Graphics User Manual
Page 300

13-75
EQP LOGIC EDITOR
Version 6.0
Item 54 - Calibration Gas Type
Calibration gas type is selected with this code.
Description
Mode
Same as Measured (Default)
1
Methane
2
Propane
3
Item 55 - Calibration Method
Description
Code
Standard (Default)
1
Cuvett
2
Item 56 - Cuvett Length
1.0 to 150.0 mm, default 150mm
Item 57 - Calibration Gas Concentration
The allowable range is from 20 to 100% with 50% as the default.
Item 58 - Volume at LFL
Used for programming a special gas type, the default value is 5%.
Item 59 - Gas Coefficient a
Used for programming a special gas type.
Item 60 - Gas Coefficient b
Used for programming a special gas type.
Item 61 - Gas Coefficient c
Used for programming a special gas type.
Item 62 - Gas Coefficient d
Used for programming a special gas type.
Item 63 - Gas Coefficient e
Used for programming a special gas type.
Item 64 - Device Removed
The user sets this bit when the device has been removed from the system. Configuration information shall be
retained in the controller to allow the device to be added at a later time. If the removed bit is set when program
mode is exited, the status will be saved during a power cycle.
This item is used to tell the controller a device has been removed from the network. The controller will signal the
“Extra LON Device” fault if the device is on-line with the removed item is set.
Item 65 - Static Logic Inverted
Setting this item tells the controller invert the signal when used with-in static logic. This can be used to have a
normally energized controller relay or a normally active digital input.
DEVICE ITEM NUMBER DESCRIPTIONS