Alarm Trigger Direction
In addition, each alarm has a checkbox to choose a “Falling Trigger”
alarm type.
When selected, the alarm will activate when the analog value drops
below the setpoint as its value is falling.
In the default configuration, a rising value activates the alarm as it passes
through the setpoint.
Gas Mode
Each channel can be configured to be used with a “Gas Detector” or
“Other (Non Gas)” instrument.
When a channel is configured as “Other” it can be used to monitor virtually
any linear analog value from a wide range of temperature, pressure, level
and other transmitter types.
When configured as a gas detector, regulatory requirements will preset
alarm setpoint ranges and certain alarm characteristics.
Common Settings
The bottom of the “AIM Editor...” dialog box contains buttons for setting all of the common settings on the
device.
Alarms
Selecting this button opens the “Alarms to Monitor...” dialog box.
This scrolling list displays the alarms and events related to the device that can be configured to be monitored