Eqp logic editor, Item 17 - current time and date, Item 18 - user name – Det-Tronics S3 Graphics User Manual
Page 294: Item 19 - controlnet mac address, Item 20 - serial port 1 protocol, Item 21 - serial port 1 baud rate, Item 22 - serial port 1 parity, Item 23 - serial port 1 address, Item 24 - allow lon point disabling, Device item number descriptions

13-69
EQP LOGIC EDITOR
Version 6.0
Item 17 - Current Time and Date
The controller real time clock can be set or read with this variable.
Item 18 - User Name
Name of the user that was logged into S
3
when the project was built.
Item 19 - ControlNet MAC Address
The ControlNet MAC address is set with this variable. Allowable values range from 1 to 99.
Item 20 - Serial Port 1 Protocol
The second serial port protocol is set with this variable.
Serial Port Protocols
Value
Description
1
Port not used
2
Modbus Slave
3
Modbus Master
Item 21 - Serial Port 1 Baud Rate
Serial baud rate for the controller RS485 serial port is set with this variable. The default baud rate is 9600.
Baud Rate Codes
Code
Speed
1
2400
2
4800
3
9600
4
19.2K
5
38.4K
6
57.6K
7
115.2K
Item 22 - Serial Port 1 Parity
The controller second serial port parity setting is set with this variable. The default parity is “None”.
Item 23 - Serial Port 1 Address
The address field is only used for Modbus protocol. Valid Modbus addresses are in the range from 1 to 247. The
default address is 1.
Item 24 - Allow LON Point Disabling
If this variable is set true, LON device disabling will be allowed. This feature has not been implemented, at this
time disabling is always allowed.