13-72
EQP LOGIC EDITOR
Version 6.0
DEVICE ITEM NUMBER DESCRIPTIONS
Item 38 - Input Static Logic Mode
Input mode is used to determine if static logic should activate controller alarms on input activation. For example,
if mode 1 is selected, static logic will activate the controller fire alarm when the input is activated.
Mode
Definition
0
Invalid
1
Fire Alarm
2
Trouble
3
Low Gas Alarm
4
High Gas Alarm
5
Supervisory
6
Other
Item 39 - UV Sensitivity
Sensitivity
Value
Definition
Standard Mode
Star Mode
1
Low
96 cps
96 cups
2
Medium (Default)
48 cps
48 cps
3
High
24 cps
24 cps
4
Very High
8 cps
8/16 cps
Item 40 - Time Delay
Valid times are from 0 to 7 seconds with a default value of 5 seconds. This item is typically used to adjust the
amount of time a fire must persist before it is deemed to be an actual fire.
Item 41 - UV Arc Rejection
UV Arc Rejection
Value
Definition
Gate Length
1
Low
0.250
2
Medium (Default)
0.125
3
High
0.0625
4
Very High
0.0625
Item 42 - UV Processing Mode
UV processing mode can be selected with this variable.
UV Processing Mode
Value
Definition
0
Standard
1
STAR
DEVICE ITEM NUMBER DESCRIPTIONS