Eqp logic editor – Det-Tronics S3 Graphics User Manual
Page 303

13-78
EQP LOGIC EDITOR
Version 6.0
Item 91 - Flame Detector Counts per Second
This variable represents the counts per second from flame detectors.
Item 92 - Supply Voltage
Field device supply voltage as measured at the device can be read with this item.
Item 93 - Wrong Device Type
This item is reserved to signal that the controller has detected a wrong device type (Not supported in the first
release).
Item 94 - Extra LON Device
This item is used to signal that the controller has detected an extra device on the LON.
Item 95 - Logic Error Reference Number
If the controller detects an error in user logic, the last trace number is stored in this item.
Item 96 - Logic Error Code
If the controller detects an error in user logic, an error number is stored in this item.
Logic Error Code
0
No Error
1
Unknown Instruction Type
2
Unsupported Address Mode
3
Unsupported Data Type
4
Unsupported Instruction
5
A parameter error was detected
6
Too many items on the stack for this opera-
tion
7
User Program is too large
8
First Scan Program Too Large to Complete
9
Initial CRC was Incorrect
10
Failed Background CRC test
11
Instruction Pointer Error
Item 97 - Memory Fault
When this item is true, a fault has been detected in the memory system.
Item 98 - RTC Fault
When this item is true, the real time clock needs to be set, or the clock circuitry has malfunctioned.
Item 99 - LON Ground Fault
When this item is true, the controller has detected a ground fault.
Item 100 - Duplicate Address
Not supported.
Item 101 - LON A Interface Fault
This bit is set when a problem is detected with LON interface channel A.
DEVICE ITEM NUMBER DESCRIPTIONS