EAGLE QUANTUM PREMIER DEVICES
Version 6.0
EAGLE QUANTUM PREMIER DEVICES
Alarm Condition
Single Zone Mode
Upon receipt of an alarm from an activated detector on IPM channel 4 or 5 OR activation of the manual station,
channel 2:
Signal circuit devices are activated per the software selected signaling circuit configuration described earlier –
Bell Circuit (SAM) Channel 6.
Programmed release time delay activated.
Release output(s) activated.
Operation of Abort: Discharge is aborted ONLY when alarm is from a detector, and abort is activated during
programmed release time delay. Abort sequence is dependent on the abort mode selection as described
earlier.
Cross Zoned Mode
Upon receipt of an alarm from one activated detector in one zone.
Signal circuit devices are activated per the software selected signaling circuit configuration, two zone mode, one
zone in alarm, as described earlier – Bell Circuit (SAM) Channel 6.
Second Alarm Condition
Upon receipt of an alarm from a second activated detector in the other zone.
Signal circuit devices are activated per the software selected signaling circuit configuration, two zone mode, two
zones in alarm.
Programmed release time delay activated.
Release output(s) activated.
Manual Alarm Condition – Cross Zoned Mode
Upon receipt of a manual alarm from Channel 2 the signal circuit devices are activated per the software selected
signaling circuit configuration, two zone mode, two zones in alarm.
Programmed release time delay activated.
Release output(s) activated.
Signaling Circuit Operation – Bell Circuit (SAM), Channel 6
This output channel can be software selected to any standard EQP Signal Audible Module (SAM) configuration.
In a cross-zoned mode, selections re limited as follows:
IPM • ALARM CONDITION