Eqp logic editor – Det-Tronics S3 Graphics User Manual
Page 302

13-77
EQP LOGIC EDITOR
Version 6.0
Item 79 - CPU Fault
The item indicates a problem with a processor or memory system, the cause of this fault is device dependent.
Item 80 - Supervisory
This item tracks the state of the controller Supervisory LED and relay, if programmed for the alternate function.
Item 81 - Channel Active
This item tracks the state of an I/O channel.
Item 82 - Control Message Fault
This item is set when a field device does not receive the output control message from the controller.
Item 83 - Channel Shorted
This item indicates when an I/O channel is shorted.
Item 84 - Channel Open
This item indicates when an I/O channel is open.
Item 85 - Channel Isolated
This item indicates when an I/O channel is isolated.
Item 86 - Normalized Process Variable
Normalized process variable holds the analog value read from the device as a floating point value. For devices
with adjustable ranges, values are calculated by using the zero and full scale range values.
Item 87 - Raw Process Variable:
Raw process variable holds the analog value read from the device as an integer value. For devices with adjustable
ranges, values are calculated by using the zero and full scale range values. When the raw integer format is used
values are in the range of 0 to 4095. Values for an ideal 4 to 20 mA sensor are:
DCU Process Variable
Input
Output
0 mA
0
4 mA
682
12 mA
2048
20 mA
3413
24 mA
4095
Item 88 - AC Voltage
The AC voltage can be read with this variable.
Item 89 - Temperature
The temperature in degrees C can be read with this variable.
Item 90 - Battery Current
This variable represents the battery charge or discharge current level. Positive values indicate battery charging
while negative values represent battery discharge.
DEVICE ITEM NUMBER DESCRIPTIONS
DEVICE ITEM NUMBER DESCRIPTIONS