EAGLE QUANTUM PREMIER DEVICES
12-83
EAGLE QUANTUM PREMIER DEVICES
Version 6.0
Abort Mode
The IPM abort input, Channel 1, is software configurable to use any one of three modes of operation. These three
modes operate as follows:
Mode 1
Upon activation, the delay timer will count down to and hold at 10 seconds; upon release, timer will continue to
count down to zero.
Note
only this mode complies with UL 864.
Mode 2
Upon activation the delay timer will reset to its initial value and on release will continue counting down to zero.
IRI Mode
Functions similar to “Mode 1” except the abort will only function if activated prior to a second alarm.
Zone Modes
The IPM has two “zone modes”; Single or Cross Zoned. The backup logic will execute differently depending on
the zone mode selected.
IPM • CONFIGURATION
IPM • CONFIGURATION