Eqp logic editor, Item 309 - one zone bell tone, Item 310 - two zone bell tone – Det-Tronics S3 Graphics User Manual
Page 320: Item 311 - manual release delayed, Item 312 - serial port 2 protocol, Item 313 - serial port 2 baud rate, Device item number descriptions

13-95
EQP LOGIC EDITOR
Version 6.0
Item 309 - One Zone Bell Tone
This item is used to select the bell tone when one zone of the IPM is in alarm and embedded logic mode is
enabled.
Value
Tone
0
Off
1
Continuous
2
60 BPM
3
120 BPM
4
Temporal
5
Trouble
6
Supervisory
Item 310 - Two Zone Bell Tone
This item is used to select the bell tone when the second zone of the IPM is in alarm and embedded logic mode
is enabled. See Item 309 for a list of available tones. The Marketing specification states that “The software will
prevent both selections (309 and 310) from being the same”.
Item 311 - Manual Release Delayed
First used with the IPM to select if the manual release input should be delayed or not. When set, the release
output will be delayed by the selected time, if cleared the release is immediate.
Item 312 - Serial Port 2 Protocol
The second configurable serial port protocol is set with this variable.
Serial Port Protocols
Value
Description
1
Port not used
2
Modbus Slave
3
Modbus Master
Item 313 - Serial Port 2 Baud Rate
The baud rate for the second configurable serial port is set with this variable. The default baud rate is 9600.
Baud Rate Codes
Code
Speed
3
9600
4
19.5K
5
38.4K
6
57.6K
7
115.2K
8
230.4K
DEVICE ITEM NUMBER DESCRIPTIONS