Sensitivity and Arc Rejection
The detector sensitivity and arc rejection settings are adjusted using the four position sliders provided in the
configuration dialog box.
The factory default for both is “High” which responds to a 1 x 1 foot n-Heptane fire at 60 feet in 1 second with
standard processing. For other fuels, distances, etc. Refer to the Appendix in the UV X2200 instruction manual
95-8549.
Combined settings
Alarm LED Latch: The tri-color LED on the face of the detector turns red when in alarm and can be configured
to be either latching or non-latching.
If latching is selected, following a fire detection, the LED will stay on until the detector is reset from the point
display for the detector in the S
3
software. The default is non-latching.
PV Deadband
Normally all values are transmitted to the controller every five seconds; If the PV changes more than the entered
percentage before the five second report time arrives, an immediate message is sent with the current values.
Time Delay
An input time delay can be programmed by entering a value from 1 to 15 seconds in the provided field. This will
delay sending the fire alarm message to the EQP controller until the fire alarm has been generated uninterrupted
for the specified time. This programmable delay can be used to filter out spurious events.