Static logic mode (input), Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual
Page 192

EAGLE QUANTUM PREMIER DEVICES
12-77
EAGLE QUANTUM PREMIER DEVICES
Version 6.0
Static Logic Mode (Input)
If the channel is configured as an input, a pull down menu will allow any of five different “static logic” functions
to be assigned, or, to select “Other” which is the default and has no automatic function.
The five static logic functions are:
Fire Alarm
Sets off the “Fire Alarm” LED and relay* on the EQP controller.
Trouble
Sets off the “Trouble” LED and relay* on the EQP controller.
Low Gas Alarm
Sets off the “Low Gas” LED and relay* on the EQP controller.
High Gas Alarm
Sets off the “High Gas” LED and relay* on the EQP controller.
Supervisory
Sets off the “Supr” LED and relay* on the EQP controller.
If a static logic function has been selected for an input, when the input is active that action will occur automatically
without the need for any user programmed logic. If the input is to be used with user programmed logic only,
select “Other”.
Alarms
Selecting this button opens the “Alarms to Monitor...” dialog box. This scrolling list displays the alarms and
events related to the device that can be configured to be monitored by S