Page 312

13-87
EQP LOGIC EDITOR
Version 6.0
Item 195 - No Oi High Energy Fault
A field device sets this status bit to indicate that the No Oi High Energy Fault is true.
Item 196 - Flash Fire
A field device sets this status bit to indicate that it has detected a flash type fire.
Item 197 - Bin Fire
A field device sets this status bit to indicate that it has detected a bin type fire.
Item 198 - Low Level Fire
A field device sets this status bit to indicate that it has detected a low level type fire.
Item 199 - Non-Ratio Mode Fire
A field device sets this status bit to indicate that it has detected a non-ratio mode type fire.
Item 200 - Quick Fire
A field device sets this status bit to indicate that it has detected a quick type fire.
Item 201 - AM/PM
This variable is intended for use by user logic to determine the time of day, 1 equals PM and 0 is AM.
Item 202 - Day of Week
This variable is intended for use by user logic to determine the day of week, the value is 1 for Sunday and 7 for
Saturday.
Item 203 - Device Download Active
The controller sets this variable while it is downloading configuration information.
Item 204 to 215 - User Defined Status 1 to 12
User defined status is provided as a method to exchange information between the controller and the ControlNet
interface. Information placed here is transmitted on ControlNet along with other scheduled data. See the
ControlNet specifications for more details.
Item 216 - Logic Engine Fault
The controller sets this variable true when a fault is detected in the user program.
Item 217 - ControlNet Firmware Version
This variable hold the firmware version of the ControlNet board.
Item 218 - Activate Trouble Tone
Setting this control bit will cause the field device output to output the trouble pattern.
Item 219 - Activate Supervisory Tone
Setting this control bit will cause the field device output to output the supervisory pattern.
Item 220 - Request Alarm Logs
Setting this control bit will cause the controller to retrieve the alarm logs from a device.
Item 221 - Request Calibration Logs
Setting this control bit will cause the controller to retrieve the calibration logs from a device.
DEVICE ITEM NUMBER DESCRIPTIONS
DEVICE ITEM NUMBER DESCRIPTIONS