Configuration, Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual
Page 219

12-104
EAGLE QUANTUM PREMIER DEVICES
Version 6.0
EAGLE QUANTUM PREMIER DEVICES
Tagname
The tagname at the top of the dialog box refers to the entire module.
Each of the two input channels also require a tagname and until one is entered, that channel is not available in
the S
3
database for programming, monitoring or dynamic graphic purposes.
Configuration
Enter the Tagname for the module, a miscellaneous description and then the tagnames and descriptions for the
two input channels.
Until tagnames are assigned to the two input channels they are not available in the S
3
database for programming
in the user logic.
Static Logic Mode (Input)
Each of the two inputs has a pull down menu that allows one of five different “static logic” functions to be
assigned, or, to select “Other” which is the default and has no automatic function.
The five static logic functions are:
Fire Alarm
Sets off the “Fire Alarm” LED and relay* on the EQP controller.
Trouble
Sets off the “Trouble” LED and relay* on the EQP controller.
Low Gas Alarm
Sets off the “Low Gas” LED and relay* on the EQP controller.
High Gas Alarm
Sets off the “High Gas” LED and relay* on the EQP controller.
Supervisory
Sets off the “Supr” LED and relay* on the EQP controller.
IDC • CONFIGURATION