Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual
Page 197

12-82
EAGLE QUANTUM PREMIER DEVICES
Version 6.0
EAGLE QUANTUM PREMIER DEVICES
Tagname
The tagname at the top of the dialog box refers to the entire module.
Each of the eight channels also require a tagname and until one is entered, that channel is not available in the S
3
database for programming, monitoring or dynamic graphic purposes.
Type
The channel type on the IPM is preset and not user changeable.
Supervision
Via a pull down menu, the inputs and outputs may be software configured to supervise their attached device.
Available supervision options include “None”, “Open Circuit” detection, “Open and Short” circuit detection.
Activation Time
If a channel is configured as an output, an “Activation Time” (in seconds) can be entered. The value is in seconds.
This feature works in conjunction with the user program to simplify the logic and protect the field device.
When being programmed in the controller, if this channel is selected as a “Timed” output then the value entered
in the “Activation Time” field determines how long the output remains energized, even if the user logic keeps the
output energized.
IPM • CONFIGURATION