Total Access 1248 Octal T1 IMA DSLAM with Modem Installation and Maintenance Practice
3-12
61179641AL4-5B
Alarm Connections
The Total Access 1248 provides an alarm port (see
) with three auxiliary alarm
inputs and three alarm outputs (Major, Minor, and Critical). Alarm inputs are activated by
shorting A and B contacts (closing an externally connected relay). The outputs provide both
normally open and normally closed pins (through internal relay contacts) for proper operation
with a variety of alarm panels. Each alarm event generates an autonomous TL1 message that
is transmitted via the in-band management channel to a monitoring device.
A cable with a high density DB-15 male connector on one end and a stub at the other end is
available (P/N 1196DB901L1) for wire-wrap connections to an alarm panel.
Figure 3-8. Total Access 1248 Alarm Connection
The alarm pinouts are shown in
.
Table 3-3. Alarm Pinouts
Pin
Color
Contact Description
1
Red
Alarm 3 Input - A
2
Red/Black
Alarm 1 Input - B
3
Red/White
Critical Alarm COM
4
Orange
Minor Alarm COM
5
Orange/Black
Major Alarm COM
6
White
Alarm 3 Input - B
7
White/Black
Alarm 2 Input - A
8
Black
Critical Alarm NC
9
Black/White
Minor Alarm NC
10
Blue/Black
Major Alarm NC
11
Blue/White
Alarm 2 Input - B
12
Blue
Alarm 1 Input - A
13
Green/Black
Critical Alarm NO
14
Green/White
Minor Alarm NO
15
Green
Major Alarm NO