4. Commissioning

4−19

Festo P.BE−SPC200−SMX−1−EN en 0503b

Determined number of revolutions and run−up
period

From the set application data the maximum number of revolĆ
utions as well as the run−up period are determined and indiĆ
cated:

Value

Description

Revolution

Number of revolutions with the configured maximum speed and resolution:

Example:

Revolution

+

ResolutionĂwithĂfullĂstep

< MaximumĂacceleration

Steps

ńturn

Revolution

+

6.25

1

mm

< 1000

mm

m

< 0.2

m

s

< 60

s

min

200

1

U

+ 375 turns

min

Run−up period

Time, in which the drive with the max. acceleration configured reaches the maxiĆ
mum speed:

Example:

Run

* upĂperiod +

MaximumĂvelocity

MaximumĂacceleration

Run

* upĂperiod +

0.2

m

s

2.0

m

s2

+ 0.1s

Reference travel mode

Mode with which reference travel is to be carried out. This
pre−setting applies to reference travel which has been
started:
ć in the dialogue window Commissioning the stepping

motor" (Command [Online] [Commission] [Stepping
motor]Ă),

ć or with the control panel.

Permitted: 0 ... 4

With command G74 the reference travel mode in the NC proĆ
gram will be defined individually.