11.1 PIN CODE OUTPUT IN WIEGAND MODE

The system transmits keypad PINs while operating in Wiegand
mode by processing any digit sequence terminated with the [*] key
as 26-bit Wiegand data. The current facility code (set using Code
32 - 2) will be used. Entering any PIN over 65535 will cause an
error condition and no data will be sent.

Because keypad data is sent in a card data format, it may not be
possible for some panels to perform CARD AND CODE operation
(requiring both) to gain access. If your panel cannot accept and
interpret 26-bit format as PIN data, be sure to configure the user at
the PC host software by entering the code into the CARD data
field for that user, not the keypad PIN number field.

11.2 LED Control Options for Wiegand Mode

The combined programming for Options 30#9 – 30#12 and the
Wiegand LED Control line affect the LED display in Wiegand
mode. The following table shows how the LED will behave when
the LED control line is open (normal) or grounded (asserted by the
access control panel).

G = Green, R = Red, Y = Yellow. See the following section for
more on option programming.

Opt 9

0 0 0 1 1 1 1 1 1

Opt 10

- - - 0 0 0 1 1 1

Opt 11

0 1 1 0 1 1 0 1 1

Opt 12

- 0 1 - 0 1 - 0 1

Led Ctl Open

G G R R Y

Led Ctl Gnd

G R Y R G