HID EDGE EVO EH400-K Standard Controller Installation Guide User Manual
Edge evo, Standard networked controller, Specifications
EDGE EVO is the next evolution in access control hardware solutions. A true IP solution that meets the demands of open architecture,
IP-centric environments, EDGE EVO provides fully distributed intelligence and decision making right to the door, leveraging the IT
infrastructure to the maximum extent possible. Leveraging Power-over-Ethernet (PoE), EDGE EVO reduces door installation costs by not
requiring a separate local power supply under many circumstances.
The Standard Networked Controller is a fully integrated single-door controller offering discrete I/O and Wiegand/Clock-and-Data interfaces
to readers. Additionally, connect native Hi-O devices (readers, locks, pushbuttons) and EDGE EVO Hi-O Modules to the Hi-O bus,
providing secure communication around the door. Hi-O involves devices with built-in intelligence and a CANbus that links all the devices
together. Password protect or encrypt Hi-O CANbus data traffic. Each Hi-O device (such as the REX switch, electric strike, card reader and
door operator) is connected to the CANbus by a single, four-wire cable. Two of the wires supply power and the other two are used for data
communication.
Specifications
CONDITIONS
VOLTAGE DC
(VDC)
CURRENT
(Amp)
OPERATING
TEMPERTURE CABLE LENGTH
UL REF
NUMBER
Input
DC Input (NSC)
+12VDC
0.18Amp
32° - 122°F
(0° - 50° C)
Hi-O CAN Bus Total Length 100 ft (30 m) -
22 AWG ● 0.65mm ● 0.33mm
2
Maximum between drops 30 ft (10 m)
22 AWG ● 0.65mm ● 0.33mm
2
RJ45
328 ft (100 m)
- Category 5 K
KE400CxNN
x =
K for Black
G for Grey
+24VDC
0.14Amp
PoE
(+48VDC NOM)
.085Amp
DC Input (MAX)
+12VDC
1.5Amp
+24VDC
1.5Amp
PoE
+48VDC (NOM)
0.3Amp
Supervised inputs
(AC, Batt, REX, Door Mon) (MAX)
0-+5VDC Reference
0.005Amp (sink)
Data 1/CLK , Data 0 / Data (MAX)
0-+5VDC Reference
N/A
Ouput
GRN LED, RED LED, Beep,
Hold (MAX)
0-+5VDC reference
0.005Amp (sink)
External Tamper (MAX)
+5VDC (NOM)
0.02
CAN DC
Output
(MAX)
AUX 12 / 24VDC Input
+10.8 to +24VDC
1.2Amp *
PoE Input
+ 24VDC (NOM)
0.4Amp *
Reader
DC PWR
Output
(MAX)
AUX 12 VDC
+9.8 to +12.25VDC
0.32Amp *
AUX 24VDC
+9.8 to +12.25VDC
0.60Amp *
PoE Input
+9.8 to +12.25VDC
0.58Amp *
Strike
/ AUX
Relays
NC or NO
DC Output
(MAX)
AUX 12VDC
Input
Unregulated (Wet)
Jumpers
+10 to 12VDC
0.70Amp *
AUX 24VDC
Input
Unregulated (Wet)
Jumpers
+23 to 24VDC
0.70Amp *
Regulated (Wet)
Jumpers - 12VDC
+10 to 12VDC
0.70Amp *
PoE Input
Unregulated (Wet)
Jumpers
+16.5 to 24VDC
0.36Amp *
Regulated (Wet)
Jumpers - 12VDC
+10 to 12VDC
0.58Amp *
AUX / PoE
Input
Jumpers Set to Dry
+12 to 24VDC
External
2.00Amp **
NSC = Normal Standby Condition
*
Combined output ratings, not to exceed 1.2 Amp
**
Each Relay