HID EDGE EVO EWM-M Wiegand Module Installation Guide User Manual
Edge evo, Specifications, Door & reader module
The EDGE EVO Door and Reader module is designed for interfacing with the EDGE EVO Hi-O Networked Controller to electronic door
components and a traditional Wiegand reader.
Designed for providing interface to traditional discrete access inputs and outputs, the Door component provides four analog/digital inputs
and two outputs. Configure the Door component in two ways; as a primary door interface to REX, Door Position Switch, Battery Fail, Power
Fail, Lock, and Aux (Group 1) or as a general purpose input/output module (Group 2).
Configure the Reader Module in two ways, either a Group 1 or Group 2 device. When two readers are present at one access control point,
the secure reader side is assigned Group 1.
Specifications
Door Module
CONDITIONS
VOLTAGE DC
(VDC)
CURRENT
(Amp)
POWER
(W)
OPERATING
TEMPERTURE CABLE LENGTH
UL REF
NUMBER
Input
DC Input (NSC)
+12 VDC
0.04 Amp
0.48
32° - 122°F
(0° - 50° C)
Inputs
= 500 ft (150 m)
Outputs
= 500 ft (150 m)
Hi-O CAN Bus Total Length 100 ft (30 m) -
22 AWG ● 0.65mm ● 0.33mm
2
Maximum between drops 30 ft (10 m)
22 AWG ● 0.65mm ● 0.33mm
2
MEDMAxNN
x = K for Black
G for Grey
+24 VDC
0.04 Amp
0.96
DC Input (MAX)
+12 VDC
0.80 Amp
9.6
+24 VDC
0.80 Amp
19.2
Supervised inputs
(AC, Batt, REX, Door Mon) (MAX)
0-5 VDC
Reference
0.005 Amp
(Sink)
0.025
Output
Strike *** /
AUX
NC or NO
DC Output
(MAX)
AUX 12 VDC
Input @
Controller
Unregulated (Wet)
Jumpers
+10 to +12 VDC 0.70 Amp*
8.40
AUX 24VDC
Input @
Controller
Unregulated (Wet)
Jumpers
+23 to +24 VDC 0.70 Amp*
16.80
Regulated (Wet)
Jumpers – 12 VDC
+10 to +12 VDC 0.70 Amp*
8.40
PoE Input @
Controller
Unregulated (Wet)
Jumpers
+16.5 to 24 VDC 0.30 Amp*
7.2
Regulated (Wet)
Jumpers – 12 VDC
+10 to +12 VDC 0.50 Amp*
6.0
AUX 12-24 VDC
/ PoE Input @
Controller
Jumpers Set to Dry
+12 to 24 VDC
External
2.00 Amp**
24.00
Reader Module
CONDITIONS
VOLTAGE DC (VDC) CURRENT
(Amp)
POWER
(W)
OPERATING
TEMPERTURE CABLE LENGTH
UL REF
NUMBER
Input
DC Input (NSC)
+12 VDC
0.03 Amp
0.36
32° - 122°F
(0° - 50° C)
Wiegand
= 500 ft (152.4 m) - 22 AWG ● 0.65mm ● 0.33mm
2
MEWMAxNN
x = K for Black
G for Grey
+24 VDC
0.72
DC Input (MAX)
+12 VDC
0.70 Amp
8.4
+24 VDC
16.8
Data 1/CLK , Data 0/Data (MAX) 0-5 VDC Reference
N/A
N/A
Output
Reader PWR
Output VDC
(MAX)
AUX 12 VDC
@ Controller
+9.8 to +12.25 VDC
0.30 Amp*
3.67
AUX 24 VDC
@ Controller
0.60 Amp*
7.35
PoE Input @
Controller
0.50 Amp*
6.12
GRN LED, RED LED,
Beep and Hold (MAX)
0-5 VDC Reference
0.005 Amp
(sink)
0.025
External Tamper - (MAX)
+5 VDC (NOM)
0.017Amp
0.085
NSC = Normal Standby Condition
** Each Relay
* Combined output rating not to exceed V*I = W
*** Shared between relays
1.2 Amp (+24VDC AUX Input, 28.8 W)
1.2 Amp (+12VDC AUX Input, 12.96 W)
EDGE EVO
®
Door & Reader Module
EDWM-M
I
nstallatIon
G
uIde
82363-901, Rev C.1
December 2012
© 2009 - 2012 HID Global Corporation. All rights reserved.
15370 Barranca Parkway
Irvine, CA 92618-2215
USA