EDGE EVO is the next evolution in access control hardware solutions. A true IP solution that meets the demands of open architecture,

IP-centric environments, EDGE EVO provides fully distributed intelligence and decision making right to the door, leveraging the IT

infrastructure to the maximum extent possible. Wire the EDGE EVO device to Hi-O interface modules providing connectivity to electronic

door components and access control readers.
Hi-O involves devices with built-in intelligence and a CANbus that links all the devices together. Password protect or encrypt Hi-O CANbus

data traffic. Each Hi-O device (such as the push plate, electric strike, card reader and door operator) is connected to the CANbus by a

single, four-wire cable. Two of the wires supply power and the other two are used for data communication.

Specifications

CONDITIONS

VOLTAGE DC (VDC)

CURRENT
(Amp)

OPERATING
TEMPERTURE

CABLE LENGTH

UL REF
NUMBER

Input

DC Input (NSC)

+12 VDC

0.14 Amp

32° - 122°F

(0° - 50° C)

Hi-O CAN Bus

Total Length 100 ft (30 m) -

22 AWG ● 0.65mm ● 0.33mm

2

Maximum between drops 30 ft (10 m)

22 AWG ● 0.65mm ● 0.33mm

2

RJ45

= 328 ft (100 m) - Category 5 K

E400CxNN

+24 VDC

0.08 Amp

PoE (+48VDC NOM)

0.05 Amp

DC Input (MAX)

+12 VDC

1.5 Amp

+24 VDC

1.5 Amp

PoE (+48 VDC NOM)

0.3 Amp

Ouput

CAN DC
Output
(MAX)

AUX 12 / 24 VDC Input

+10.8 to +24 VDC

1.2 Amp*

PoE Input

+ 24 VDC (NOM)

0.4 Amp*

NSC = Normal Standby Condition

* Combined output ratings are not to exceed 1.2 Amps (AUX Input) or 0.4 Amps (PoE Input).

X = K for Black

G for Gray

EDGE EVO

®

Hi-O Networked Controller

EH400

I

nstallatIon

G

uIde

82000-920, Rev C.0

October 2011

© 2009 - 2011 HID Global Corporation. All rights reserved.

15370 Barranca Parkway
Irvine, CA 92618-2215
USA