Specifications

CONDITIONS

VOLTAGE DC

(VDC)

CURRENT

(Amp)

POWER

(W)

OPERATING

TEMPERTURE CABLE LENGTH

UL

REFERENCE

NUMBER

Input

DC Input (NSC)

+12 VDC

0.04 Amp 0.48

32° - 122°F

(0° - 50° C)

Lock Control Circuit

100 ft (30 m) = 22 AWG ● 0.65mm ● 0.33mm2

200 ft (60 m) = 18 AWG ● 1.02mm ● 0.82mm2

Hi-O CAN Bus Total Length 100 ft (30 m) -

22 AWG ● 0.65mm ● 0.33mm2

Maximum between drops 30 ft (10 m)

22 AWG ● 0.65mm ● 0.33mm2

ELMAxNN

X = K for Black

G for Gray

+24 VDC

0.04 Amp 0.96

DC Input (MAX)

+12 VDC

1.2 Amp

14.4

+24 VDC

1.2 Amp

28.8

Output

DC Output

(MAX)

AUX 12 VDC

Input @

Controller

Unregulated Jumpers

+10 to +12 VDC 0.46 Amp* 5.52

AUX 24 VDC

Input @

Controller

Unregulated Jumpers

+23 to +24 VDC 1.0 Amp*

24.0

Regulated Jumpers – 12 VDC

+10 to +12 VDC 1.0 Amp*

12.0

PoE Input @

Controller

Unregulated Jumpers

+16.5 to 24 VDC 0.30 Amp* 7.2

Regulated Jumpers – 12 VDC

+10 to +12 VDC 0.60 Amp* 7.2

Output Power Selection

P103

1 & 2

2 & 3

12 VDC

CAN / DC Input

Mounting

EDGE EVO

®

L

ock

M

oduLe

ELM

I

nstallatIon

G

uIde

82301-901, Rev C.1

December 2012

© 2009 - 2012 HID Global Corporation. All rights reserved.

15370 Barranca Parkway

Irvine, CA 92618-2215

USA

NSC = Normal Standby Condition
* Combined output rating not to exceed V*I = W

1.2 Amp (+24 VDC AUX Input, 28.8 W)

1.2 Amp (+12 VDC AUX Input, 12.96 W)

CAUTION: Some magnetic locks exhibit both high inrush current when activated and a high instantaneous

break voltage when de-energized due to magnetic field collapse. It is recommended you use of a snubber circuit

across the controlling relay terminals to protect the controlling relay contacts. Go to support.hidglobal.com, see

Solution 891 - How do I wire a High In-Rush Current locking device to VertX/EDGE EVO. Not evaluated by UL.

This Hi-O interface module is wired to interface the EDGE EVO device

(Controller/Reader & Module or Networked) with electronic door components.

The Lock module provides outputs to an electronic locking device.

Install the EDGE EVO Lock Module within

a UL Listed single-gang electrical box or

optionally within a hollow metal door frame

(shown).